T15BRInstallation ManualEnglishMAEN165,2014-04
Installation5.Connect the cables in the specified order, according to the drawing and stepsbelow.Caution:• The operator panel mustbe brought toambient
Installation2.2.2 HazardousLocationInstallationConnect the desired cables and attach them to strain relief plate with cable tiesprovided.2.2.3 OtherCo
Technical Data3TechnicalDataParameter T15BRFrontpanel,W×H×D 410×286×83mmCut out dimensions,W×H394 ±1 mm× 270±1 mm. Maximum corner radius: 4 mm.ForIP66
Technical DataParameter T15BRActiveareaofdisplay, W × H331.2× 207.0mmOperatingtemperatureMinimumtemperature:-30 °CMaximum temperature:70 °C; UL 65 °CS
Chemical Resistance4 ChemicalResistance4.1 MetalCasingThe frame and casing material is powder-coated aluminum. This powder paintwithstands exposure to
Chemical Resistance4.2 TouchScreenandO verlay4.2.1 AutoflexEBAutoflex EB covers the overlay surrounding the screen.SolventResistanceAutoflex EB withstand
Chemical Resistance4.2.2 TouchScreenSurfaceThe touch screen surface on the operator panel withstands exposure to thefollowing solvents without visible
Chemical Resistance4.3 TerminaltoPanelGasketThe gasket is made of flame retardant silicone rubber. The sealing capability isunaffected by the following
Operator Panel Drawings5 Opera torPanelDrawings5.1 ConnectorsPos. Connector Description1 Powersupply +12–+24VDC(10–32VDC)2 COM 1 RS232 CommunicationPo
Operator Panel Drawings5.3 T15BROutline 286 410 7 max. 8mm 76 9 9 392 9 268 9 B CEDAEA. ConnectorsB. SD memory card slotC. USB hostD. Expansio
ForewordInstallationmanualforT15BRForewordAll operator panels are developed to satisfy the demands of human-machinecommunication. Built-in functions s
Additional Installation Tips6 AdditionalInstallationTipsWhen experiencing communication problems in for example noisy environmentsor when operating cl
Additional Installation TipsNote:The grounding wiresshould beshort andthe conductorshould havea large area.A long, thin grounding wirehas a very high
Additional Installation TipsA good solution may be to use a shielded Ethernet cable, but to co nnect the shieldat one end only.One option is to break
Additional Installation Tips6.3 ToAchieveBetterEMCProtection• Use shielded cables for RS232 communication.• Use twisted pair and shielded cabling for
Additional Installation Tips6.4 AmbientTemperatureThe maximum ambient temperature for the operator panel is provided in thespecifications. The ambient
Additional Installation Tips6.5 SafetyMost of the operator panels are fed with 24 V DC.412434Power supply230 V AC to 24 V DCPower supply230 V AC to 24
Additional Installation Tips6.6 GalvanicIsolationInternal electronicsVCC0 V (GND)Filter+24 V DC0 Vgalvanic isolationgalvanic isolationRS422/485 RS422
Additional Installation Tips6.7 CableandBusTerminationRS485• Use shiel ded and twisted pair cable. The pair c apacitance may not exceed52.5 pF/m and a
HeadofficeBeijerElectronics ABBox 42620124Malmö,Swedenwww.beijerelectronics.com / +4640 358600
ContentsContents1 Safety Precautions ... 41.1 General ...
Safety Precautions1SafetyPrecautionsBoth the in staller and the owner and/or operator of the operator panel must readand understand this installation
Safety PrecautionsWarning:Do not disconnect equipment unlesspower hasbeen removed or the areaisknownto be non-hazardousAVANT D E DECONNECTER L’EQUIPEM
Safety Precautions1.3 HighPotentialTestingEach terminal is high-pot (high potential) tested prior to shipmen t. After high-pottesting surge arresting
Safety Precautions1.7 DismantlingandScrapping• The operator panel or par ts thereof shall be recycled according to localregulations.• The following co
Installation2Installation2.1 SpaceRequirements• Maximum installation plate thickness: 8 mm• Space requirements in millimeters when installing the oper
Installation2.2 InstallationProcessA Thumb Screw Installation Tool (provided) or a slotted screwdriver is requiredfor installation.1.Unpack and check