UserGuideRevision1.12
www.beijerelectronics.com
2
IP20QuickStartUpGuide
ACSupplyConnectionSupplyVoltage
3PhaseUnits:ConnectL1L2L3,PE 200240Volts+/‐10%
1PhaseUnits:ConnectL1,L2,PE 380380Volts+/‐10%
FusesorMCB
o ChecktheDriveRatingInformationonpage48
HelpCard
Display
KeypadOperationcanbefoundonpage27
IMPORTANT!
HardwareEnableCircuit
Linktheterminalsasshown,optionallythroughswitchcontactsto
enabledriveoperation
ControlTerminals
Basedonthefactorydefaultparametersettings

RunStop 10KSpeedPot
Closetheswitchto run(enable),opentostop
MotorCable
o Forcorrectcablesize,seeTechnicalDataonpage48
o Observethemaximumpermissiblemotorcablelength
o ForMotorcablelengths>50metres,anoutputfilteris
recommended
o
Useascreened(shieldedcable)
MotorConnection
CheckforStarorDeltaConnection
EntertheMotorNameplateDataintothedriveParametersasfollows
o MotorRatedVoltage:P107
o MotorRatedCurrent:P108
o MotorRatedFrequency:P109
o MotorRatedSpeed(Optional)
:P110
FusesorMCB
M