5.10. TerminalControl
Whendelivered,theDriveisinthefactorydefaultstate,meaningthatitissettooperateinterminalcontrolmodeandallparametershavethe
defaultvaluesasindicatedinsection6.
• Connectthedrivetothesupply,ensuringthecorrectvoltageandfusing/circuitbreakerprotection–see
section10.2.
• Connectthemotortothedrive,ensuringthecorrectstar/deltaconnectionforthevoltagerating‐seesection4.6.
• Applythemainspowertothedrive,thenenterthemotordatafrommotornameplate;P1‐07=motorratedvoltage,P1‐08=motor
ratedcurrent,P1‐
09=motorratedfrequency.
• ConnecttheDriveHardwareEnable(STO)circuitasfollows(seesection0forfurtherdetails)
o LinkTerminal1toTerminals12(STO+)
o LinkTerminal9toTerminal13(STO‐)
• Connectacontrolswitchbetweenthecontrolterminals1and2ensuringthat
thecontactisopen(drivedisabled).
• Connectapotentiometer(1kΩminto10kΩmax)betweenterminals5and7,andthewipertoterminal6.
• Withthepotentiometersettozero,switchonthesupplytothedrive.Thedisplaywillshow
StoP.
• Closethecontrolswitch,terminals1‐2.Thedriveisnow‘enabled’andtheoutputfrequency/speedarecontrolledbythe
potentiometer.ThedisplayshowszerospeedinHz(
H 0.0)withthepotentiometerturnedtominimum.
• Turnthepotentiometertomaximum.Themotorwillaccelerateto50Hz,(60HzforHPdrives),thedefaultvalueofP1‐01,underthe
controloftheaccelerationramptimeP1‐03.
• Ifthepotentiometeristurnedtominimum,themotorwilldecelerate
to0Hz,thedefaultminimumspeedsetinP1‐02,underthe
controlofthedecelerationrampP1‐04.Theoutputspeedcanbeadjustedanywherebetweenminimumandmaximumspeedusing
thepotentiometer.
• Todisplaymotorcurrent(Amps),brieflypressthe (Navigate)key.
• Press againtodisplaythemotorpower.
• Press
againtoreturntospeeddisplay.
• Tostopthemotor,disablethedrivebyopeningthecontrolswitch(terminals1‐2).
• Iftheenable/disableswitchisopenedthedrivewilldeceleratetostopatwhichtimethedisplaywillshow
StoP.