Beijer-electronics BFI-P2 V1.21 Manuel d'utilisateur Page 38

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 56
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 37
UserGuideRevision1.12
www.beijerelectronics.com
38
Par ParameterName Minimum Maximum Default
P214 AnalogOutput2(Terminal11)Format SeeBelow
U 0-10
‐
U 0-10 =0to10V.
U 10-0=10to0V,
A 0-20=0to20mA
A 20-0=20to0mA
A 4-20 =4to20mA
A 20-4=20to4mA
P215 UserRelay1Output(Terminals14,15&16)Functionselect 0 13 1 ‐
SelectsthefunctionassignedtoRelayOutput1.Therelayhasthreeoutputterminals,Logic1indicatestherelayisactive,and
thereforeterminals14and15willbelinkedtogether.
0:DriveEnabled(Running).Logic1whenthemotorisenabled
1:DriveHealthy.Logic1whenpoweris
appliedtothedriveandnofaultexists
2:AtTargetFrequency(Speed).Logic1whentheoutputfrequencymatchesthesetpointfrequency
3:OutputFrequency>0.0Hz.Logic1whenthedriveoutputfrequencytothemotorisexceeds0.0Hz
4:OutputFrequency>=Limit.Logic1whenthemotorspeedexceedstheadjustablelimit
5:OutputCurrent>=Limit.Logic1whenthemotorcurrentexceedstheadjustablelimit
6:OutputTorque>=Limit.Logic1whenthemotortorqueexceedstheadjustablelimit
7:AnalogInput2SignalLevel>=Limit.1Logicwhen
thesignalappliedtotheAnalogInput2exceedstheadjustablelimit
Note:Whenusingsettings47,parametersP216andP217mustbeusedtogethertocontrolthebehaviour.Theoutputwill
switchtoLogic1whentheselectedsignalexceedsthevalueprogrammedin
P216,andreturntoLogic0whenthesignalfallsbelow
thevalueprogrammedinP217.
8:Reserved.NoFunction
9:Reserved.NoFunction
10:Reserved.NoFunction
11:Reserved.NoFunction
12:DriveTripped.Logiconewhenthedrivehastrippedandthedisplayshowsthefaultcode.
13:STOStatus.Logic1whenbothSTOinputsarepresentandthedriveisabletobeoperated
P216 AdjustableThreshold1UpperLimit(AnalogOutput1/RelayOutput1) P217 200.0 100.0 %
P217 AdjustableThreshold1LowerLimit(AnalogOutput1/RelayOutput1) 0.0 P216 0.0 %
UsedinconjunctionwithsomesettingsofParametersP211&P215.
P218 UserRelay2Output(Terminals17&18)Functionselect 0 8 0 ‐
SelectsthefunctionassignedtoRelayOutput2.Therelayhastwooutputterminals,Logic1indicatestherelayisactive,and
thereforeterminals17and18willbelinkedtogether.
0:DriveEnabled(Running).Logic1whenthemotorisenabled
1:DriveHealthy.Logic1whenpowerisappliedtothedriveandnofaultexists
2:AtTargetFrequency(Speed).Logic1whentheoutputfrequencymatchesthesetpointfrequency
3:OutputFrequency>0.0Hz.Logic1whenthedriveoutputfrequencytothemotorisexceeds0.0Hz
4:OutputFrequency>=Limit.Logic1whenthemotorspeedexceedstheadjustablelimit
5:OutputCurrent>=Limit.Logic1whenthemotorcurrentexceedstheadjustablelimit
6:OutputTorque>=Limit.Logic1whenthemotortorqueexceedstheadjustablelimit
7:AnalogInput2SignalLevel>=Limit.1Logicwhen
thesignalappliedtotheAnalogInput2exceedstheadjustablelimit
8:HoistBrakeControl.Therelaycanbeusedtocontrolthemotorholdingbrakeonahoist.
Note:Whenusingsettings47,parametersP219andP220mustbeusedtogetherto
controlthebehaviour.Theoutputwill
switchtoLogic1whentheselectedsignalexceedsthevalueprogrammedinP219,andreturntoLogic0whenthesignalfallsbelow
thevalueprogrammedinP220.
9:Reserved.NoFunction
10:Reserved.NoFunction
11:Reserved.
NoFunction
12:DriveTripped.Logiconewhenthedrivehastrippedandthedisplayshowsthefaultcode.
13:STOStatus.Logic1whenbothSTOinputsarepresentandthedriveisabletobeoperated
P219 AdjustableThreshold1UpperLimit(AnalogOutput2/RelayOutput2) P220 200.0 100.0 %
P220 AdjustableThreshold1LowerLimit(AnalogOutput2/RelayOutput2) 0.0 P219 0.0 %
UsedinconjunctionwithsomesettingsofParametersP213&P218.