iXPanelT60Service&MaintenanceManualEnglishMAEN005,2010-05
Installation3Installation3.1 SpaceRequirements• Installation plate thickness: 1.5 - 7.5 mm (0.06 - 0.3 inch)• Space requirements when installing the o
Installation2.Place the panel cut out where the operator panel is to be situated, draw alongthe outer sides of the holes and cut according to the mark
Installation4.Connect the cables in the specified order, according to the drawing and stepsbelow.Caution:• Ensurethattheoperatorpanelandthecontrollersy
Installation3.2.1 ConnectionstotheControllerFor information about the cables to be used when connecting the operator panel tothe controller, please re
Technical Data4TechnicalDataParameter iX Panel T60Frontpanel,WxHxD 202x152x6mmMountingdepth 57mm(157mmincludingclearance)Frontpanelseal IP66Rear panel
Chemical Resistance5 ChemicalResistance5.1 MetalCasingThe frame and casing material is powder-coated aluminum. This powder paintwithstands exposure to
Chemical Resistance5.2 TouchScreenandOverlay5.2.1 AutotexF157/207Autotex F157 or F207 covers the overlay surrounding the touch screen.SolventR esistan
Chemical Resistance5.2.2 TouchScreenSurfaceThetouchscreensurfaceonthepanelwithstandsexposuretothefollowingsolvents without visible change:Solvents Tim
Hardware Tests6 HardwareTestsBefore the operator panels are approved for market introduction, they are testedby independent authorities. The iX Panels
Hardware Replacement7 HardwareReplacementThis section contains instructions on how to replace operator panel hardware.Only components included in the
ForewordService&MaintenancemanualforiXPanelT60ForewordThis manual contains detailed information about iX Panel T60, includingdescriptions of vario
Hardware ReplacementMODE Description1110 Self-test.xxx1 Hardreset(forcesthesystemtorese t).To ch ange mode switches, follow the steps below:1.Disconne
Hardware Replacement7.3 ReplacingtheRearCoverThe following is needed:• Anewrearcover,seeAvailable Spare Parts for iX Panel T60• AtorxT10screwdriverNot
Hardware Replacement7.4 ReplacingtheDisplay/DisplayCableThe following is needed:• A new display including display frame, seeAvailable Spare Parts for
Hardware Replacement7.Insert the two screwdrivers between the display frame and the aluminumcasingillustratedbelow. Pressandbendgentlyonthedisplayfram
Hardware Replacement7.5 ReplacingtheCompleteFrontThe following is needed:• Anewfront,seeAvailable Spare P arts for iX Panel T60• AtorxT10screwdriverNo
Hardware Replacement7.6 ReplacingtheBatteryThe following is needed:• Anewbattery,seeAvailable Spare Parts for iX Panel T60Note:MakesuretouseadequateES
Hardware Replacement7.7 ReplacingtheBacklightIf the backlight of the iX Panel T60 is broken, the entire display must be replaced.To replace the displa
Hardware Replacement7.8 AvailableSparePartsforiXPanelT60Ordernumber Description601009280 COMPLETEFRONTIncludingfrontcover,touchoverlay,gasketsandlabel
Service Menu8ServiceMenuThe service menu for the operator panel can be accessed before a project isdownloaded, or by setting the mode switches in mode
Service Menu8.3.3 EraseProjectThe erase function will detect if the project is located in the panel memory or on amemory card. Pressing Erase Project
ContentsContents1 Safety Precautions ... 51.1 General ...
Hardware Self Test9 HardwareSelfTestThe self-test program can be used to test aspects of operator panel functionalityand the communication ports. To r
Additional Installation Tips10 AdditionalInstallationTipsWhen experiencing communication problems in for example noisy environmentsor when operating c
Additional Installation Tips10.2 EthernetConnectioninthePanel123451-12-23-38-8RJ45RJ45RJ45RJ45RJ45RJ45RJ45RJ45Industrial EthernetOperator panelOperato
Additional Installation Tips10.3 ToAchieveBetterEMCProtection• Initially, use the original cabling from Beijer Electronics primarily.• Use shielded ca
Additional Installation Tips10.4 AmbientTemperatureThe maximum ambient temperature for the operator panel is provided in thespecifications. The ambient
Additional Installation Tips10.5 SafetyMost of the operator panels are fed with 24 V DC.412434Power supply230 V AC to 24 V DCPower supply230 V AC to 2
Additional Installation Tips10.6 GalvanicIsolationUSBUSBRS232RS422/485+24 V DC0 VFilterDC/DCgalvanic isolationVCC0 V (GND)DC/ACCFLEthernetInternal ele
Additional Installation Tips10.7 CableandBusTerminationRS485• Use shielded and twisted pair cable. The pair capacitance may not exceed 52.5pF/m and ar
Fault Tracing11 FaultTracingThis section includes different fault scenarios and steps to follow to trace the fault.TheiXPanelT60isnotworkingproperly,a
Fault TracingTheiXPanelT60isworking,butoneormorekeysarenotworking1.Check that the flex cables are correctly fitted.2.Replace the front according to the
Contents9 Hardware SelfTest ... 3010 Additional Installation Tips ...
Software12 SoftwareThis chapter describes how to maintain and update the software in the iX Panels.The chapter includes a general description of the o
Software12.2 UpdateSoftwareWhen an update is available, an e-mail is sent to the distributors. The software isalso available on the manufacturer’s web
SoftwareTransferImage1.Double-click on the executable Image Loader file to start the transfer program.2.Follow the instructions.The image transfer proc
Environmental Aspects13 EnvironmentalAspectsThis chapter includes inform ation about the environmental impact of iX Panels.More information can be fou
Environmental Aspects13.3 RecyclingThe operator panels consist largely of aluminum. It is a great advantage in terms ofboth resources and the environm
HEADOFFICE SUBSIDIARIESSWEDEN GERMANY USABeijerElectronicsProductsAB Elektronik-SystemeLauerGmbH&Co. KG BeijerElectronicsInc.Box426 Kelterstraße59
Safety Precautions1SafetyPrecautionsBoth the installer and the owner and/or operator of the operator panel must readand understand this installation m
Safety Precautions1.3 DuringUse• Keep th e operator panel clean.• Emergency stop and other safety functions may not be controlled from theoperator pan
Introduction2IntroductionThis manual describes how to maintain the iX Panel T60.The functions available in iX Developer depend on which operator panel
Introduction2.2 MaintenanceCarefully read the instructions before beginning maintenance on the operatorpanel.• Only qualified personnel should carry ou
Introduction2.5 ContactandSupportIf you want to report a fault or have a question about the operator panels, pleasecontact your local supplier or fill
Commentaires sur ces manuels