Vue de la page 7
Installation
4.
Connect the cables in the specified order, according to the drawing and steps
below.
Caution:
Ensurethattheoperatorpanelandthecontrollersystemhavethesameelectrical
grounding(referencevoltagelevel),otherwiseerrorsincommunicationmay
occur.
Theoperatorpanelmustbebroughttoambienttemperaturebeforeitisstarted
up. Ifcondensationforms,ensurethattheoperatorpanelisdrybeforeconnecting
ittothepowero utlet.
Ensurethatthevoltageandpolarityofthepowersourceiscorrect.
Useonlyshieldedcommunicationcables.
Separatehighvoltagecablesfromsignalandsupplycables.
24V DC
RS422/
RS485
RS232
24V DC
A
C
D
Controller
Power
B
Ethernet
Connect cable A.
Connect cable B, using an M5 screw and a grounding conductor (as short
as possible) with a cross-section of minimum 2.5 mm
2
.
Connect cable C.
Connect cable D.
5.
Carefully remove the laminated lm over the operator panel dis play, to avoid
static electricity that could damage the panel.
BeijerElectronics, MAEN997
8